Voltage Drop Calculator

Check how much voltage a wire run loses on the way to its load. The voltage drop calculator works for copper or aluminium wire in AWG or mm², for single-phase and three-phase supplies, and shows the percentage lost.

Supply
Conductor
Wire size system
Length units

Line-to-line for three-phase.

Voltage drop

2.02%

2.42 V is lost along the run, leaving 117.6 V at the load. That is within the 3% guide for a branch circuit.

Volts dropped
2.42 V
Voltage at the load
117.6 V
Resistance, one way
0.0605 Ω
Against the 3% guide
Within 3%

This tool estimates voltage drop only. It does not replace local wiring rules. Work on mains wiring must be done by a licensed electrician.

How to use this calculator

  1. 1 Choose single-phase or three-phase, then copper or aluminum for the conductor.
  2. 2 Pick the wire size in AWG or mm², and enter the one-way length of the run.
  3. 3 Enter the current the load draws, and the supply voltage.
  4. 4 Read the percentage drop and the voltage left at the load. Compare the result with your local wiring rule.

What is voltage drop?

Every wire has some resistance, so some of the voltage is used up as the current flows along it. This loss is called voltage drop. The voltage that reaches the load is lower than the voltage at the source.

A small drop is normal. A large drop makes lights dim, motors run hot and heaters work less well. It can also mean the wire is too thin for the current it carries.

How the drop is calculated

The current must travel to the load and back, so a single-phase circuit counts the length twice. The ohms law calculator covers the same relationship between voltage, current and resistance. The drop is 2 × current × resistance of the one-way wire. For three-phase, the calculator uses the square root of 3 instead of 2.

Resistance depends on the wire size and the metal. Copper has lower resistance than aluminum of the same size, so aluminum needs a larger wire for the same drop. The calculator uses resistance values at a conductor temperature of 75 °C.

Wire sizes and metric equivalents

In North America, wire is sized in AWG, where a higher number means a thinner wire. In most other countries, wire is sized by its cross-section in square millimetres, where a bigger number means a thicker wire.

Use the size list that matches your cable markings. The calculator converts the length for you, so you can enter feet or metres. For a quick check of length units, the unit converter helps.

What is a safe voltage drop?

Many wiring guides suggest keeping the drop within 3% for a branch circuit, and within about 5% for the whole run from the supply. The calculator uses 3% as its guide. Other national wiring rules, such as BS 7671 in the United Kingdom, set their own limits and methods.

A drop above the guide is not always dangerous, but it is a sign to check the wire size, the length and the load. Your local rules have the final say.

Electrical safety for wire runs

An undersized wire can overheat, and that can start a fire. Always size wire to the rules in your area, not only to the voltage drop. Protect the circuit with a breaker or fuse of the right rating.

Mains wiring must be done by a licensed electrician. Switch off and isolate the supply before you touch any cable, and never work on a live circuit. To estimate what the load uses, the electricity calculator and the resistor calculator give useful figures.

The formula

Single-phase drop

Drop = 2 × current × resistance

current
the current the load draws, in amps
resistance
the one-way resistance of the wire, in ohms

Three-phase drop

Drop = √3 × current × resistance

√3
about 1.732, used for three-phase supplies

Percentage

Percentage drop = (drop ÷ supply voltage) × 100

supply voltage
the voltage at the start of the run

Worked example

10 AWG copper wire, 50 ft long, carrying 20 A on a 120 V single-phase supply

  1. 1.Resistance, one way: 1.21 ohms per 1,000 ft × 50 ft ÷ 1,000 = 0.0605 ohm, using the table value for 10 AWG copper
  2. 2.Drop: 2 × 20 × 0.0605 = 2.42 volts
  3. 3.Percentage: 2.42 ÷ 120 × 100 = 2.02%
  4. 4.Voltage at the load: 120 − 2.42 = 117.6 volts

The drop is 2.02%, which is within the 3% guide.

Frequently asked questions

What is an acceptable voltage drop?

A common guide is 3% on a branch circuit and about 5% for the whole run. Local wiring rules set the official limit, so check them. This calculator uses 3% as its guide.

Does copper or aluminum lose more voltage?

For the same size, aluminum has higher resistance and loses more voltage. An aluminum wire therefore often needs one size larger than copper for the same drop.

Why is three-phase drop calculated differently?

Three-phase supplies share the load across three conductors, so the current in each wire is calculated with the square root of 3 instead of 2.

Can I use this to pick a wire size for my house?

Use it as a check. Wire size must also meet current rating, protection and installation rules. A licensed electrician should size and install mains wiring.

Sources

Last reviewed by the GridCalculators team.